PDU 1PH, 230V AC, 16A, 21x C13 3x C19, 3.
search
  • PDU 1PH, 230V AC, 16A, 21x C13 3x C19, 3.
  • PDU 1PH, 230V AC, 16A, 21x C13 3x C19, 3.
PDU 1PH, 230V AC, 16A, 21x C13 3x C19, 3.
PDU 1PH, 230V AC, 16A, 21x C13 3x C19, 3. PDU 1PH, 230V AC, 16A, 21x C13 3x C19, 3.

PDU 1PH, 230V AC, 16A, 21x C13 3x C19, 3.7kVA Outlet Metered and Switched, Zero U vertical

€1,875.00
Tax excluded

1PH, 230V AC, 16A (16A rated); 24 outlets: 21x C13, 3x C19; plug: IEC 60309 2P+E 6h 16A (Bottom-bottom feed), 3.7kVA; Outlet Metered/Switched, Zero U vertical PDU, SecureLock ready, high resolution color display with field replaceable controller, Ethernet, serial, 2x USB-A, USB-B and sensor connections

Quantity

1PH, 230V AC, 16A (16A rated);

24 outlets: 21x C13, 3x C19;

plug: IEC 60309 2P+E 6h 16A (Bottom-bottom feed), 3.7kVA;

Outlet Metered/Switched,

Zero U vertical PDU,

SecureLock ready,

high resolution color display with field replaceable controller,

Ethernet, serial, 2x USB-A, USB-B and sensor connections

Features

Energy Metering: Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor

Metering Accuracy: ISO/IEC 62053-21 1%

Remote Outlet Switching: Yes

Metering per input line: Yes

Metering per Branch Circuit Breaker: No

Environmental Sensor Ready: Yes

Compatible Sensors: Temperature, Humidity, Air Flow, Differential Pressure, Water Leak, and Contact Closure.

PDU Linking: Link up to 8 PDUs where the Primary PDU has knowledge and power information from the attached Expansion PDUs. Redundant power from the first expansion unit ensures uptime even if the Primary PDU loses power.

Cascading: Physically cascade 32 PDUs under one ethernet port or 16 PDUs with USB using bridging mode, or additionally, save IP addresses using a single IP address with port forwarding.

Networking: (10/100/1000 Base T) Ethernet, Secondary redundant (10/100/1000 Base T) Ethernet. Optional WiFi (802.11 a/b/g/n).

Onboard Display: Color, matrix LCD display : Voltage, current, or active power (per line, per breaker, or per receptacle / outlet); Alarms; Configuration information (name, ratings, IP / Networking information). Auto-flip orientation

 

Raritan
PX3-5487-M11

Data sheet

Phase
1
Volt
230
Ampère
16
Number of outlets
24
Type outlets
C13, C19
Inlet plug
IEC 60309
kVA
3.7
Type
Outlet Metered and Switched
Form
0U
Cord length
3
Dimensions
52mm x 65mm x 1298mm