PDU 1PH, 230V AC, 32A, 24 outlets 20x C13 4x C19, 7.4kVA Unit Metered, Zero U vertical
1PH, 230V AC, 32A (32A rated); 24 outlets: 20x C13, 4x C19; plug: IEC 60309 2P+E 6h 32A (Top-top feed), 7.4kVA; Unit Metered, Zero U vertical PDU, SecureLock ready, high resolution color display with field replaceable controller, Ethernet, serial, 2x USB-A, USB-B and sensor connections
Monitored rack power distribution unit (0U [vertical], 7.4kVA, 24 outlets).
INPUT: 230v, 32a - IEC 60309 2P+E 6h 32A plug (2P3W);
OUTPUT: 20x C13, 12x C19 outlets; on 2x 1-pole, 16a Overcurrent Protectors;
Billing-Grade (+/- 1%) Energy Metering [kW, kVA, V, A, Power Factor] - per inlet, per breaker/fuse;
Remote network monitoring via HTML, JSON-RPC, SSH, Telnet, MODBUS/TCP, and SNMPv3.
Onboard embedded processor with minimum 536MHz clock speed, 16MB SPI Flash, and 64MB DDR2 RAM.
Cascading upto 16 PDU's using single Ethernet or USB connection.
Environmental monitoring [temp/humidity] capable – up to 32 sensors.
Individual outlet numbers labeled on chassis.
Automated deployment via TFTP, DHCP, SSH(CLI), or USB Flash Drives.
WiFi Capable.
USB Webcam Capable.
iPad/iPhone/Android App.
Dual 10/100/1000 Ethernet port.
Breaker metering and alarming (0V detection).
Max Dimensions 52mm x 55mm x 1539mm (2.1in x 2.2in x 60.6in).
Max Weight TBD.
Maximum ambient temperature 60C at full load.
Features
Energy Metering: Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor
Metering Accuracy: ISO/IEC 62053-21 1%
Remote Outlet Switching: No
Metering per input line: Yes
Metering per Branch Circuit Breaker: No
Environmental Sensor Ready: Yes
Compatible Sensors: Temperature, Humidity, Air Flow, Differential Pressure, Water Leak, and Contact Closure.
PDU Linking: Link up to 8 PDUs where the Primary PDU has knowledge and power information from the attached Expansion PDUs. Redundant power from the first expansion unit ensures uptime even if the Primary PDU loses power.
Cascading: Physically cascade 32 PDUs under one ethernet port or 16 PDUs with USB using bridging mode, or additionally, save IP addresses using a single IP address with port forwarding.
Networking: (10/100/1000 Base T) Ethernet, Secondary redundant (10/100/1000 Base T) Ethernet. Optional WiFi (802.11 a/b/g/n).
Onboard Display: Color, matrix LCD display : Voltage, current, or active power (per line, per breaker, or per receptacle / outlet); Alarms; Configuration information (name, ratings, IP / Networking information). Auto-flip orientation
Data sheet
- Phase
- 1
- Volt
- 230
- Ampère
- 32
- Number of outlets
- 24
- Type outlets
- C13, C19
- Inlet plug
- IEC 60309
- kVA
- 7.4
- Type
- Unit Metered
- Form
- 0U
- Cord length
- 3
- Dimensions
- 52mm x 55mm x 1539mm