PDU 3PH, 400V AC, 32A, 24x C13 12x C19, 22.2kVA Outlet Metered, Zero U vertical
3PH, 400V AC, 32A (32A/PH rated); 36 outlets: 24x C13, 12x C19; plug: IEC 60309 3P+N+E 6h 32A (Wye Bottom-bottom feed), 22.2kVA; Outlet Metered, Zero U vertical PDU, SecureLock ready, V2 Outlet Sequence, high resolution color display with field replaceable controller, Ethernet, serial, 2x USB-A, USB-B and sensor connections
Monitored rack power distribution unit (0U [vertical], 22.2kVA, 36 outlets).
INPUT: 400v (3-phase WYE), 32a - IEC 60309 3P+N+E 6h 32A plug (4P5W);
OUTPUT: 24x C13, 12x C19 outlets; on 6x 1-pole, 16a Overcurrent Protectors;
Billing-Grade (+/- 1%) Energy Metering [kW, kVA, V, A, Power Factor] - per inlet, per breaker/fuse, per outlet, Residual Current Monitoring Supported;
Remote network monitoring via HTML, JSON-RPC, SSH, Telnet, MODBUS/TCP, and SNMPv3.
Onboard embedded processor with minimum 536MHz clock speed, 16MB SPI Flash, and 64MB DDR2 RAM.
Cascading upto 16 PDU's using single Ethernet or USB connection.
Environmental monitoring [temp/humidity] capable – up to 32 sensors.
Individual outlet numbers labeled on chassis.
Automated deployment via TFTP, DHCP, SSH(CLI), or USB Flash Drives.
WiFi Capable.
USB Webcam Capable.
iPad/iPhone/Android App.
Dual 10/100/1000 Ethernet port.
Tri-color status LED per receptacle.
Breaker metering and alarming (0V detection).
Max Dimensions 52mm x 65mm x 1780mm (2.1in x 2.6in x 70.1in).
Max Weight 7 kg.
Maximum ambient temperature 60C at full load.
Features
Energy Metering: Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor
Metering Accuracy: ISO/IEC 62053-21 1%
Remote Outlet Switching: No
Metering per input line: Yes
Metering per Branch Circuit Breaker: No
Environmental Sensor Ready: Yes
Compatible Sensors: Temperature, Humidity, Air Flow, Differential Pressure, Water Leak, and Contact Closure.
PDU Linking: Link up to 8 PDUs where the Primary PDU has knowledge and power information from the attached Expansion PDUs. Redundant power from the first expansion unit ensures uptime even if the Primary PDU loses power.
Cascading: Physically cascade 32 PDUs under one ethernet port or 16 PDUs with USB using bridging mode, or additionally, save IP addresses using a single IP address with port forwarding.
Networking: (10/100/1000 Base T) Ethernet, Secondary redundant (10/100/1000 Base T) Ethernet. Optional WiFi (802.11 a/b/g/n).
Onboard Display: Color, matrix LCD display : Voltage, current, or active power (per line, per breaker, or per receptacle / outlet); Alarms; Configuration information (name, ratings, IP / Networking information). Auto-flip orientation
Data sheet
- Phase
- 3
- Volt
- 400
- Ampère
- 32
- Number of outlets
- 36
- Type outlets
- C13, C19
- Inlet plug
- IEC 60309
- kVA
- 22.2
- Type
- Outlet Metered
- Form
- 0U
- Cord length
- 3
- Dimensions
- 52mm x 65mm x 1780mm