PDU 3PH, 400V AC, 32A, 32A,/PH, rated 36 outlets 30x C13 6x
search
  • PDU 3PH, 400V AC, 32A, 32A,/PH, rated 36 outlets 30x C13 6x
PDU 3PH, 400V AC, 32A, 32A,/PH, rated 36 outlets 30x C13 6x

PDU 3PH, 400V AC, 32A, 32A,/PH, rated 36 outlets 30x C13 6x C19, 22.2kVA Unit Metered, Zero U vertical

€ 1.630,00
Exclusief belasting

3PH, 400V AC, 32A (32A/PH rated); 36 outlets: 30x C13, 6x C19; plug: Cord (Wye Bottom-bottom feed), 22.2kVA; Unit Metered, Zero U vertical PDU, SecureLock ready, V2 Outlet Sequence, high resolution color display with field replaceable controller, Ethernet, serial, 2x USB-A, USB-B and sensor connections

Aantal

Monitored rack power distribution unit (0U [vertical], 22.2kVA, 36 outlets).

INPUT: 400v (3-phase WYE), 32a - Hardwired [Unterminated Cord, No Plug];

OUTPUT: 30x C13, 6x C19 outlets; on 6x 1-pole, 16a Overcurrent Protectors;

Billing-Grade (+/- 1%) Energy Metering [kW, kVA, V, A, Power Factor] - per inlet, per breaker/fuse, Residual Current Monitoring Supported;

Remote network monitoring via HTML, JSON-RPC, SSH, Telnet, MODBUS/TCP, and SNMPv3.

Onboard embedded processor with minimum 536MHz clock speed, 16MB SPI Flash, and 64MB DDR2 RAM.

Cascading upto 16 PDU's using single Ethernet or USB connection.

Environmental monitoring [temp/humidity] capable – up to 32 sensors.

Individual outlet numbers labeled on chassis.

Automated deployment via TFTP, DHCP, SSH(CLI), or USB Flash Drives.

WiFi Capable.

USB Webcam Capable.

iPad/iPhone/Android App.

Dual 10/100/1000 Ethernet port.

Breaker metering and alarming (0V detection).

Max Dimensions 52mm x 55mm x 1780mm (2.1in x 2.2in x 70.1in).

Max Weight TBD.

Maximum ambient temperature 60C at full load.

Kenmerken

Energy Metering: Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor

Metering Accuracy: ISO/IEC 62053-21 1%

Remote Outlet Switching: No

Metering per input line: Yes

Metering per Branch Circuit Breaker: No

Environmental Sensor Ready: Yes

Compatible Sensors: Temperature, Humidity, Air Flow, Differential Pressure, Water Leak, and Contact Closure.

PDU Linking: Link up to 8 PDUs where the Primary PDU has knowledge and power information from the attached Expansion PDUs. Redundant power from the first expansion unit ensures uptime even if the Primary PDU loses power.

Cascading: Physically cascade 32 PDUs under one ethernet port or 16 PDUs with USB using bridging mode, or additionally, save IP addresses using a single IP address with port forwarding.

Networking: (10/100/1000 Base T) Ethernet, Secondary redundant (10/100/1000 Base T) Ethernet. Optional WiFi (802.11 a/b/g/n).

Onboard Display: Color, matrix LCD display : Voltage, current, or active power (per line, per breaker, or per receptacle / outlet); Alarms; Configuration information (name, ratings, IP / Networking information). Auto-flip orientation

 

Raritan
PX3-1722NV-M5V2

Datasheet

Phase
3
Volt
400
Ampère
32
Number of outlets
36
Type outlets
C13, C19
kVA
22.2
Type
Unit Metered
Form
0U
Cord length
3
Dimensions
52mm x 55mm x 1780mm

Je bent misschien ook geïnteresseerd in